Top > SDR 13.5 Hershey CPVC High Performance Fire Sprinkler System > Fire Sprinkler System CPVC Fittings

Product Name: Fire Sprinkler System CPVC Tee


Description:

  • Fire Sprinkler System pipe and fittings are designed specifically for fire sprinkler systems.


Note : Do not recommend to service or test with compressed air or gases.

Character:


  • Burning resistance

  • Low smoke toxicity

  • Easy installation

  • Light weight

  • Low friction loss

  • No rusting, pitting, scaling or corrosion, even in salt air environments

  • Immunity to Microbiologically Influenced Corrosion

  • Long life

Specifications:

SCH80

Fire Sprinkler System CPVC Tee (S * S * S)

Size

Outside Dia

Socket Type

Structure Diameter

D0

d1

d2

l

d

L

H

1/2"

32 

21.54

21.23

22.22

16.5

74.5

37

3/4"

37

26.87

26.57

25.4

24

85

42.5

1"

48.5

33.66

33.27

28.58

28

97

48

1-1/4"

55.5

42.42

42.04

31.75

35

115.5

58

1-1/2"

63.5

48.56

48.11

34.93

41

128

64

2"

75

60.63

60.17

38.1

52

146

73

2-1/2"

92

73.38

72.85

44.45

69

173

86.5

3"

109

89.31

88.70

47.63

84

197

98.5

4"

135

114.76

114.07

57.15

109

239

119.5

 

(Unit : mm)

SCH40

Fire Sprinkler System CPVC Tee (S * S * S)

Size

Outside Dia

Socket Type

Structure Diameter

D0

d1

d2

l

d

L

H

3/4"

33.5

26.87

26.57

18.26

20.5

74

37

1"

41.5

33.66

33.27

22.23

27

88

44

1-1/4"

50.5

42.42

42.04

23.83

38

99

50

 

(Unit : mm)



No.16,Jing 2nd Road, Chungkang Export Processing Zone, Wuchi Township, Taichung County 435, Taiwan, R.O.C.
TEL :886-4-2659-5377 FAX : 886-4-2659-5288
E-mail:info@hershey.com.tw